Description
range of product |
Easypact CVS100…250 |
|
---|---|---|
product or component type |
Circuit breaker |
|
device short name |
CVS100B |
|
device application |
Distribution |
|
poles description |
4P |
|
protected poles description |
3d |
|
neutral position |
Left |
|
Earth leakage protection (Vigi add on) |
Without |
|
[In] rated current |
100 A at 40 °C |
|
breaking capacity code |
B |
|
network type |
AC |
|
[Icu] Breaking capacity |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
utilisation category |
Category A |
|
trip unit name |
TM-D |
|
trip unit technology |
Thermal-magnetic |
|
trip unit rating |
100 A at 40 °C |
|
protection type |
Overload protection (thermal)
Short-circuit protection (magnetic) |
network frequency |
50/60 Hz |
|
---|---|---|
control type |
Toggle |
|
mounting mode |
Fixed |
|
mounting support |
Backplate |
|
upside connection |
Front |
|
downside connection |
Front |
|
connections – terminals |
Screw connection |
|
[Uimp] rated impulse withstand voltage |
8 kV conforming to EN/IEC 60947-2 |
|
thermal protection adjustment range |
70…100 A |
|
[Ics] rated service breaking capacity |
15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
mechanical durability |
30000 cycles |
|
electrical durability |
12000 cycles 415 V In conforming to IEC 60947-2 |
|
connection pitch |
35 mm |
|
contact position indicator |
Yes |
|
neutral protection setting |
No protection (3d) |
|
long time pick-up adjustment type Ir |
Adjustable |
|
long time pick-up adjustment range |
0.7…1 x In |
|
long time delay adjustment type |
Fixed |
|
instantaneous pick-up adjustment type Ii |
Fixed |
|
instantaneous pick-up adjustment range |
800 A |
|
height |
161 mm |
|
width |
140 mm |
|
depth |
86 mm |
|
net weight |
2.2 kg |
Avis